Welcome to the Consumer Units technical section. Currently we have information regarding the MCB's & RCD's used in consumer units. |
Minature Circuit Breakers (MCB's) |
Miniture Circuit Breakers (MCB's) are current limiting Thermal / magnetic type with each part performing a different function:
A) Small Overload Conditions
Overload currents that are light in nature are detected by a bi-metalic strip which bends at a rate dependant upon the size of the overload against a trip mechanism which will release contact after a pre-determined timescale.
B) High Overload Conditions
When the overload current reaches a high enough level (dependant upon the current rating and tripping characteristics of the MCB) the current induces a magnetic flux within the coil sufficient to propel a plunger into the tripping mechanism with enough force to operate this mechanism and trip out the MCB.
C) Short Circuit Conditions
If a fault occurs that is high enough to be classed as a 'short circuit' the the current limiting mechanism comes into action. The fault current generates so much flux in the coil that the plunger is forced to move so fast and with so much force that it i) trips the mechanism and ii) forces the contacts to open and therefore restricts the short circuit current. The arc generated between the contacts is quickly quenched by the 'Ark Grid' after it is forced to flow along the 'Arc Runners' into the Grid. |
B, C & D Curves for MCB's |
ALL MCB’s are now rated at 10kA Short
Circuit Capacity with Positive Contact Indication.
‘B’ Curve to BSEN 60898 (Magnetic Trip 3 to 5 Times In)
Used in domestic situations where the maximum
sensitivity is required and very little equipment with
high start up current is required.
‘C’ Curve to BSEN 60898 (Magnetic Trip 5 to 10 Times In)
Used in commercial/light industrial situations where close
protection is not required and start up currents of devices
can run up to 5 times rated current or a short period. Also
if many low voltage lights are used in a domestic situation
then, due to the inrush currents of the transformers type ‘C’
MCB’s may be required to avoid nuisance tripping.
‘D’ Curve to BSEN 60898 (Magnetic Trip 10 to 20 Times In)
Used in industrial situations where start-up currents
may be 10 times rated current, for example
protection for machines with electric motors fitted,
large installation with a high volume of low voltage
lighting may also require ‘D’ Curve. |
Residual Current Devices (RCD’s) |
An RCD is the term that describes a device that
opens the protected circuit when the detected
residual current exceeds that of the preset value of
the RCD. Under normal ‘healthy’ circuit conditions
with all conductors passing through the current
transformer (built into RCD, 2 &4 Pole) the vector
sum of the current values will be zero. When a fault
occurs between any phase or neutral and earth
regardless of load, this will give rise to a residual
current which will be detected by the RCD. When this
residual current exceeds the ‘Tripping Current’ (aka:
sensitivity of the RCD) the RCD will operate and
open the circuit. it is most important to connect all
Line and Neutral conductors through the RCD as one
of the most common causes of nuisance operation is
not connecting all the conductors through and RCD.
Three types of RCD are produced. Each with a
specific use:
Type AC - Tripping is ensured for residual sinusodial
alternating currents, whether the fault is suddenly
applied or is a slowly rising fault.
Type A - Tripping is ensured for residual sinusodial
alternating currents and residual pulsating direct
currents whether the fault is suddenly applied or is a
slowly rising fault.
Type S - Tripping Devices with built in ‘Time Delay’
for selectivity within circuits having more than one
RCD in line. |
Uses of RCD's |
RCD’s offer very good protection against
Earth Fault Currents, the main areas of
application are as follows:
Protection against indirect contact or
where the Zs value is too high. In Places
where overload protection cannot react
within the specified timescale due to the
earth lop impedance being too high, adding
an RCD may solve the problem without
having to make any other changes to the
system. The high sensitivity of the RCD will
ensure disconnection within the specified
time and thus without detriment to the
overload discrimination (MCB/RCD systems
only). In particular situations such as
bathrooms and building sites, use of an RCD
will help achieve the more stringent tripping
times required by regulation. At all times
to avoid the danger of exposed conductive
parts reaching unaceptably high voltage, the
rated residual operating current multiplied by
the Zs value must not exceed 50V.
Protection against Direct Contact.
In this case RCD’s offer a high level of protection
but must not be the only method of
protection. To offer this degree of protection,
the RCD must have a sensitivity of 30mA or
less and must trip-out with a residual current of 150mA in less than 40mS.
Protection against shock outside the
equipotential bonding zone.
Earth bonding is used in an installation to try and ensure that, as near as possible, all
metalic parts are maintained to the same
potential as earth. Working with portable
equipment outside the equipotential bonding
zone introduces additional shock hazards.
Any 32A or lower socket outlet that may
reasonably be expected to supply portable
equipment should be protected by a 30mA
RCD, unless using reduced voltage supplied
via an isolating transformer.
Protection for portable equipment.
The provisions of the wiring Regulations demand
the use of RCD protection to protect the
users of any such equipment with the
exception of where a socket is specifically
designed to be used outside of equipotential
bonding zone. The use of RCD’s to
control such portable equipment is widely
recognised as having greatly increased
safety in the home and the workplace.
Protection in Special Locations.
The use of RCD’s is either obligatory or strongly
recommended in the following locations:
Caravans, Shed’s, Garages or Port-acabins.
Near Swimming pools, Construction
Sites, TT wiring systems and on Farms. - at
each location a 30mA RCD should be used. |
|
|