 |
|
|
|
|
|

 |
QVS Electrical Supplies | Electrical Wholesale
Code of Practice for Inspection & Testing of Portable Electrical Equipment "PAT Testing"
 |
Code of Practice for Inspection & Testing of Portable Electrical Equipment "PAT Testing" |
 |
Untitled Document
Code of Practice for the Inspection and Testing of
Portable Electrical Equipment - "PAT Testing"
Introduction
The Health and Safety
Executive states that about one quarter of all reportable
electrical accidents at work involve portable electrical
equipment, and there are about five fatalities each year
involving such equipment.
The
majority of these accidents are entirely avoidable, and many
are due to very obvious faults in equipment.
The
purpose of these inspections and tests is to check the
electrical safety of all portable electrical equipment
regularly so that dangerous faults can be corrected before
they cause any injury.
Authorised
Testers will be appointed under the code of practice, and will
be given a written authorisation which clearly defines the
extent of the electrical inspections and tests that they are
authorised to do.
No
Authorised Tester will be expected to carry out tests on types
of equipment with which they are not familiar, or be expected
to make judgements on matters beyond their training or
experience.
Except for
replacing fuses and mains plugs, any repair work required on
equipment as a result of these inspections and tests should
not be undertaken by Authorised Testers, unless they have the
required specialist electrical knowledge and
experience.
The
initials of an Authorised Tester on a test label signify only
that the item of equipment so identified was electrically safe
in term of the inspection carried out on the stated
date.
The
Authorised Tester is not certifying the equipment to be safe
after the quoted date.
Authorised
Testers may seek further training or advice from the
University Safety Office (ext 4100).
Requirements
1. All portable
electrical equipment in the University is subject to regular
inspection and tests as in the attached schedule, with the
exception of:
(a) Rented or hired equipment or
equipment on loan. No electrical tests should be made, but a
visual inspection of the mains lead, mains plug, and integrity
of protective casing must be made, and any defects which can
not be easily corrected should be reported to the owner of the
equipment.
(b) Personal domestic equipment used by
students within their Halls of Residence is exempted, but
students are advised to maintain this equipment in a safe
condition for their own protection.
(c)
Contractor's equipment. The safety of this equipment is the
responsibility of the contractor.
(d) Computers,
electronic typewriters, etc, should not be tested with the PAT
or PAC testers, as the tests could damage the equipment. The
mains lead and plug should be inspected, and the outer casing
should be inspected for any damage.
2. Inspection
and testing will only be carried out by people nominated and
authorised as Authorised Testers.
Check List for inspections and
tests
1. Check the electrical rating
plate or Label
- Voltage - should be 230 to 250 Vac (or)
- Power Rating - should be less than 3 KW
- Protection Class - should be class I or Class
II (may be IIA or IIB)
- If Class II, the double insulation symbol must
be shown.
|
 |
2. Can the
PAT or PAC testers be used on this equipment? (See
Requirements sections a, c & d).
3. Visual
inspection
3.1 |
Disconnect
the equipment from the mains supply. |
3.2 |
Is the length
of mains lead suitable and safe for the equipment and
the way it is used? |
3.3 |
Is the mains
lead firmly connected to the equipment with a rubber or
plastic bush if it passes through a metal panel? (Try
pulling, pushing and rotating the mains
lead). |
3.4 |
Are there any
kinks or knots in the mains lead? |
3.5 |
Are there any
taped joins in the mains lead? |
3.6 |
Is the outer
insulation, including braid if present, intact and
undamaged on the whole length of the mains
lead? |
3.7 |
Is the
outside of the mains plug cracked, damaged, or very
dirty? |
Following
this inspection, replace any suspect mains plugs and arrange
for any faulty mains leads to be replaced.
4.
Internal check on mains plug
4.1 |
Is the inside
of the plug, and cover, free from cracks, burns, or
other damage? |
4.2 |
Is the cable
clamp intact and firmly gripping the outer sheath of the
mains lead? |
4.3 |
Are the cable
ends the right length, fully insulated almost to the
plug terminals, and firmly attached to the correct
terminals in the plug? Always double-check
this. |
4.4 |
Is the fuse
correctly rated for the
equipment? |
Following
this inspection replace the fuse or plug if
necessary.
5. Electrical safety
tests
These tests will use the PAT or PAC test
instruments where appropriate.
Warning Do not touch the
equipment being tested while the test is being carried
out.
| 5.1 |
Does the
equipment have a 3-core mains lead (Class I) or a 2-core
mains lead (Class II)? |
| 5.2 |
Class I
(earthed) equipment, with 3-core mains lead |
|
5.2.1 |
Using the PAT tester
Earth Bond Test - with clip lead connected to
metal case of equipment under test.
Reading should be
in green band or less than 0.1 ohm (0.3 ohm in special
cases, see note iii).
Insulation Test - disconnect
dip lead.
Equipment mains switch must be
ON.
Reading should be in green band.
No
further tests should be made. |
|
5.2.2 |
Using the PAC checker
Connect clip lead to metal case of equipment
under test.
Equipment mains switch must be
ON.
Press test button and hold until two lights show
on PAC checker.
Both lights should show
PASS.
No further tests can be
made. |
| 5.3 |
Class II
(double insulated) equipment, with 2-core mains
lead. |
|
5.3.1 |
Check that the manufacturer's double insulation
symbol is present. |
| |
|

|
|
5.3.2 |
Check that the outer casing of the equipment is
complete and undamaged. |
No
tests with PAT or PAC instruments are required on double
insulated equipment.
NB Items of Class O
equipment may sometimes be found. These have a metal outer
case, a 2-core mains lead, and do not carry the double
insulation symbol. This equipment is of foreign manufacture
and is not acceptable for use in the UK.
Class O
equipment must never be passed as safe for use by any
Authorised
Tester.
NOTES
-
Portable electrical equipment is any equipment which
connects to single-phase electrical mains supplies by a
flexible cable and a 13 Amp plug, or which plugs into an
adaptor supplied from a 13 Amp plug.
NB - Extension leads
and adaptors are included, and must be inspected and
tested.
-
Frequency of inspection and test will vary with
equipment and use (see notes on 'Not to be used after'
system).
-
Equipment with a mains lead more than 3 metres long
eg some overhead projectors, may fail the Earth Bond Test on
PAT tester because of the resistance of the mains lead. In these cases only, a reading of 0.3 ohms or less
will satisfy safety requirements.
-
If all inspections and tests are satisfactory,
fix an initialled and dated 'Not to be used after' label to
the mains lead near the plug.
-
If any inspection or test is not satisfactory, or you
are doubtful of the results:take the equipment out of use
immediately;
label the equipment to show the reason
for failure.
inform your supervisor that the
equipment is in need of repair, or more specialist
inspection, before it can be put back into
use.
-
Equipment with plug-in, removable, mains leads
This equipment should be inspected and tested
according to this Code of Practice, with the mains lead
in use at the time of test. If tests are satisfactory,
attach a 'Not to be used after' label to the mains lead, and
a second 'Not to be used after' label in a conspicuous position on the equipment. This ensures
that if labelled equipment is used with a labelled mains
lead, it is known that both have been tested. Seeing the
label on the equipment will also draw attention to the
existence of a removable mains lead.
UNIVERSITY "NOT TO
BE USED AFTER" SYSTEM
These
labels are to be used for all PAT testing and inspection
work.
The White labels are for use on
equipment where period between tests is two
years.
The Yellow labels are for use on
equipment where period between tests is one year or
less.
Designation of test
period
Two year period between tests -
will include equipment which is rarely moved or unplugged from
the supply and where the environment and use are not likely to
cause any deterioration in electrical safety.
One
year, or shorter, period between tests - will include the
majority of equipment which is unplugged and moved around very
regularly, and any equipment which is used in a hostile
environment eg exposed to moisture, heat, vibration, physical
damage, etc.
This category will include all portable
power tools, which should be inspected at no more than six
monthly intervals or even more often if used in hostile
conditions.
The label should be attached as a "flag"
with the centre of the label wrapped round the mains cable of
the equipment about three inches from the mains plug, and the
two sides of the label stuck together to show Poly logo and
title on one side and "Not to be used after" on the
other.
The label can be written on with
spirit-based permanent markers.
"Not to used
after" should show "Month" and "Year"
"Tester" -
initials of authorised tester
"Date" - date of
test
Health & Safety
Office
Codes/HS03/1997
|
|
|

4c, The Birches Industrial Estate, Imberhorne Lane, East Grinstead, East Sussex, RH19 1XZ |
Copyright © 1995-2008 QVS Electrical Supplies | Electrical Wholesale |
|